Hi,
Got a question. Building an area of my house to house a dense amount of miners. Going to dedicate about 90A of 220V to the miners and the supporting infrastructure and possible the A/C to cool them. Currently have 4 tons of cooling but that is for the whole house, so I know I will need to dedicate more A/C to the miners. MY question is usually when I build datacenter for traditional uses I estimate 3.5 BTU per watt of power, do miners fall into this same ratio of heat per watt? Since the power supplies are usually from servers/computers I am going to use that ratio on them but any help with heat generation on miners would be helpful.
Normally for datacenters I also do lights, breakers, wiring, etc, but in the case of this room in my house just worried about the computers, miners and the window. The only one I am not sure about is if the miners fall into the 3.5 ratio.
Thanks.